Microsoft word - k9947v3_reva.doc
K9947V3 5/08 Rev. A
ADEMCO 5821
Temperature Sensor & Flood Detector
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
TAMPER SUPERVISION
The ADEMCO 5821 Temperature Sensor & Flood Detector
The 5821 tamper supervision feature (Loop 4) causes a
is a wireless transmitter used with Honeywell's ADEMCO
trouble signal to be sent to the control if the unit's cover is
alarm systems that support 5800 series devices. The 5821
removed from the base or if an external probe is used and
can be configured to operate as a stand-alone temperature
the wire is cut (open) or the probe is shorted. The tamper
sensor and/or as either a Remote Temperature Sensor
or
switch is also used to program the unit's serial number and
Flood Detector. The 5821 in combination with the
loop assignments to the control panel.
ADEMCO T280R temperature probe is ideal for monitoring
SETTING THE OPERATING MODE
refrigerators and freezers in restaurants, kitchens and warehouses where food storage is a concern. The 5821 in
Table 1 provides a list of the various operating modes of the
combination with the ADEMCO 470PB probe can be used to
5821 with the respective Loop and DIP Switch settings for
sense floods in basements and other areas where there is a
each. Note that Cold Temp Sensing can be used in
possibility of flooding. The 5821 will send an alarm, via its
combination with any of the other operating modes. To use
RF transmitter, to the control when the preset temperature
the transmitter to monitor two different conditions, you
limit is exceeded or when a flood is detected. Temperature
must program each loop used on the 5821 as its own zone,
monitoring and flood detection is dependent on the
and you must set the DIP Switches as shown for the
operating mode selected. Refer to Table 1 for applicable
combination functions in Table 1.
operating modes.
PROGRAMMING THE UNIT
Room temperature is monitored at the device using the
Once you have selected an operating mode and have set the
5821's internal sensor. Refrigerator or Freezer temperature
DIP Switches accordingly, you must enroll the transmitter
is monitored remotely using the ADEMCO T280R
in the control panel. When programming the transmitter in
temperature probe. Flood detection is monitored remotely
the control panel, note that you must program a separate
using the ADEMCO 470PB probe with the supplied resistor.
zone for each loop you are using on the transmitter. To
A separate 5821 is required for each external probe being
In refrigerator or freezer applications, when the
1. Enter the control's Zone Programming mode.
temperature increases past the high threshold limit and a
2. Enter the zone number to be programmed.
delay of greater than 30 minutes passes, an alarm is
3. Enter the applicable zone type when prompted (zone
triggered. This preset delay offers greater reliability
types such as 24-Hr. Aux, Waterflow, etc. should be
against false alarms, especially due to open refrigerator or
used) depending on the function of the zone and the
control panel being used (see the control panel's instructions for available zone types and definitions).
A 3-volt lithium battery powers the 5821. If the battery voltage gets too low, the 5821 sends a low battery signal to
4. When prompted, enter Input Type 03 (3 on some
the control panel.
controls) – Supervised RF Transmitter.
5. When prompted for the serial number, transmit from
the detector by pressing the tamper switch.
INSTALLING/REPLACING THE BATTERY
6. When the serial number is displayed, transmit from the
Important Notes:
detector again by pressing the tamper switch.
• Use 3-volt lithium battery:
The current loop number (4) will begin to flash.
Duracell DL 123A or Panasonic CR123A.
7. Manually change the loop number to the desired loop
• Observe polarity.
number for the zone (according to the application—see
When replacing the battery, wait at least 30 seconds after removing the old battery, before installing the new
8. When programming for this zone is complete, program
other zones for the transmitter as necessary (each loop requires its own zone.
Install or replace the battery as follows:
9. Exit Programming mode when programming is
1. Remove the transmitter's top cover by inserting the flat
complete, and test the detector. Refer to the Testing
blade of a small screwdriver into the pry-off slot at one
end of the unit (see Figure 1 for location), and slightly twisting the blade until the cover disengages.
2. Install a 3-volt lithium battery as shown in Figure 1.
MOUNTING THE DETECTOR
To mount the detector, proceed as follows:
You can mount the 5821 on a wall or ceiling within the
1. Remove the transmitter's top cover by inserting the flat
protection area. The following notes apply:
blade of a small screwdriver into the 'pry-off' slot at one
• The 5821 may be installed in any direction.
end of the unit (see Fig. 1 for location), and slightly
twisting the blade until the cover disengages.
When used in-conjunction with the ADEMCO 470PB flood sensor probe, use no more than 48 inches of wire
IMPORTANT: DO NOT remove the circuit board from the
from the 5821 to the flood sensor and connect the
back case plastic.
termination resistor across the probes terminals.
2. Remove the battery.
• When used in-conjunction with ADEMCO T280R
3. Disengage the attached mounting plate from the case
temperature probe, use the shortest wire possible (less
by inserting the blade of a small screwdriver into the
than 96 inches) to improve the signal integrity.
locking tab release window (see Figure 1) and pressing
• Although the unit can be mounted directly to a surface,
it against the locking tab, while sliding the mounting
we recommend that the mounting plate be used for ease
plate upward along the case back until free.
of removal for servicing if necessary. Avoid mounting
4. Install the mounting plate, with its two case- holding
the detector near heat generating devices (e.g. ovens,
posts pointing up (in this example), in the location
heat vents, furnaces, boilers) or to a metal cabinet or
selected. Use the flat-head screws supplied.
5. For surface wiring entry, two thin "breakout" areas are
Wireless Transmission Path Test
provided in the case wall (see Figure 1).
A good RF transmission path must be established from the
6. Attach the case back to the mounting plate by sliding
proposed mounting location before permanently installing
the keyhole slots in the case back down onto the
the detector. To determine that there is good signal
mounting plate's case holding posts. The locking tab
reception from the proposed location, perform the test
will click as the case back locks in place.
procedure described in TESTING THE DETECTOR section.
External Probe Wiring Connections (If used)
Once a good RF transmission path is confirmed, mount the
7. With the battery still not inserted, connect the wires to
detector as follows, referring to Figure 1.
the unit's sensor terminals (see Figure 1).
8. Install the battery.
COVER PRY-OFF SLOT
IMPORTANT:
This detector should be used for property protection.
Reliance should not be placed on this detector for life safety.
When life safety is involved, smoke detectors MUST also be
used. The flood probe must not be painted.
TESTING THE DETECTOR
The test procedure should be performed to determine a good
RF transmission path and again after installation is
completed. To test,
Activate the control panel's test mode.
Activate the detector by removing and replacing
the cover. The system's keypads should beep and
each zone the 5821 is programmed for will be
Exit the control's test mode (User Code + OFF).
MAINTAINING PROPER OPERATION
To maintain the detector in proper working condition, it is
important that you observe the following:
Replace the battery when the system indicates that the
5821 reported a low battery condition.
Units should never be relocated without the advice or
assistance of the alarm service company.
Figure 1
Table 1: 5821 Operating Mode Choices
External
Operating Mode
Faults when…
Restores when…
Probe ✝
temperature drops below
temperature rises 48°F (9°C)
Cold Temp Sensing
45°F (7°C) for >10 minutes.
for >4 minutes.
temperature rises above
temperature drops below 92°F
Hot Temp Sensing
95°F (35°C) for >10 minutes. (33°C) for > 4 minutes.
Warm Temp
temperature rises above
temperature drops below 72°F
75°F (24°C) for >10 minutes. (22°C) for > 4 minutes.
temperature rises above
Freezer Temp
temperature drops below 7°F
(-14°C) for > 4 minutes.
(-12°C) for >30 minutes.
Refrig. Temp
temperature rises above
temperature drops below 39°F
42°F (6°C) for >30 minutes.
(4°C) for > 4 minutes.
external probe tips are in
probe tips have not been in
Flood Sensing
contact with water for >3
contact with water for > 3
probe shunted by
2.2MΩ resistor ✝✝
Cold Temp Sensing
temperature drops below
temperature rises 48°F (9°C)
45°F (7°C) for >10 minutes.
for >4 minutes.
Warm Temp
temperature rises above
temperature drops below 72°F
No external probe
75°F (24°C) for >10 minutes. (22°C) for > 4 minutes.
Cold Temp Sensing
temperature drops below
temperature rises 48°F (9°C)
45°F (7°C) for >10 minutes.
for >4 minutes.
Hot Temp Sensing
temperature rises above
temperature drops below 92°F
No external probe
95°F (35°C) for >10 minutes. (33°C) for > 4 minutes.
Cold Temp Sensing
temperature drops below
temperature rises 48°F (9°C)
45°F (7°C) for >10 minutes.
for >4 minutes.
Refrig. Temp
temperature rises above
temperature drops below 39°F
42°F (6°C) for >30 minutes.
(4°C) for > 4 minutes.
Cold Temp Sensing
temperature drops below
temperature rises 48°F (9°C)
45°F (7°C) for >10 minutes.
for >4 minutes.
Freezer Temp
temperature rises above
temperature drops below 7°F
10°F (-12°C) for >30
(-14°C) for > 4 minutes.
Cold Temp Sensing
temperature drops below
temperature rises 48°F (9°C)
45°F (7°C) for >10 minutes.
for >4 minutes.
Flood Sensing
external probe tips are in
probe tips have not been in
contact with water for >3
contact with water for > 3
2.2MΩ resistor ✝✝
✝ When the 5821 is used with either external probe, an open-circuit or a short-circuit of the probe's wiring results in an alarm on
that loop, and a trouble condition on all other programmed loops.
✝✝ Use a maximum wire length of 48 inches between the 5821 and the 470PB probe.
Power: 3V lithium battery
TO THE INSTALLER
(Duracell DL123A, Panasonic CR123A)
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous
CAUTION: Risk of fire, explosion, and burns. Do not
satisfactory operation of any alarm system.
recharge, disassemble, heat above 212°F
The installer should assume the responsibility of developing and
(100°C) or incinerate. Dispose of used batteries
offering a regular maintenance program to the user as well as
promptly. Keep away from children.
acquainting the user with the proper operation and limitations of
Operating Temperature: 14°F (-10°C) to 104°F
the alarm system and its components parts. Recommendations must be included for a specific program of frequent testing (at least
weekly) to ensure the system's proper operation at all times.
Operating Voltage: 3.2VDC
Dimensions:
3.1" length, 1.6"wide, 1.0"
FCC / IC STATEMENT
This device complies with Part 15 of the FCC rules and RSS210 of
Sensor Parameters:
Industry Canada. Operation is subject to the following two
Cold Temperature
conditions: (1) This device may not cause harmful interference, and
(Freeze) Detector
(2) this device must accept any interference received, including
Warm Temperature
interference that may cause undesired operation.
Detector 75°F (24°C)
Unauthorized changes or modifications could void the user's authority to operate the equipment.
Detector 95°F (35°C)
Refrigerator Failure
REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE
Detector 42°F (6°C)
CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY INFORMATION AND LIMITATIONS OF THE
ENTIRE ALARM SYSTEM.
Detector 10°F (-12°C)
Hysteresis ✝✝✝
¼ inch of water covering the probe
Response Time Tolerance ✝✝✝✝ +50%,
Temperature Measurement Accuracy (internal temp. sensor
or external temp. probe)
✝✝✝ Hysteresis is the temperature difference between "fault" and
"restore" points.
✝✝✝✝ The Response Time Tolerance is the time duration necessary
for the device to respond to a "fault" or "restore" condition. This time does not take into account the time necessary for the probe and circuitry to equalize to the ambient temperature. This feature prevents false alarms due to open doors and other transitory conditions.
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright 2008 Honeywell International Inc.
ÊK9947V3ÈŠ K9947V3 5/08 Rev. A
Source: http://www.agm.com.co/files/products/119/I-5821.pdf
Tendances Récentes Emergentes et Nouvelles Drogues Tendances récentes émergentes et nouvelles drogues Marseille 2009 – juin 2010 Présentation du dispositif TREND Marseille 2010 .7 Les espaces étudiés. 7 1.1 Espace urbain et espace festif. 7 1.2 L'expérimentation d'un élargissement du champ d'observation. 7 Les outils de recueil des données. 8
In: Handbook on Metabolic Syndrome ISBN: 978-1- 62257-025-6 Editors: C. M. Lopez Garcia and P. A. Perez Gonzalez © 2012 Nova Science Publishers, Inc. The exclusive license for this PDF is limited to personal website use only. No part of this digital document may be reproduced, stored in a retrieval system or transmitted commercially in any form or by any means. The publisher has taken reasonable care in the preparation of this digital document, but makes no expressed